Transition and turbulence

A room's warm layer stands where the vents say, whatever the heat

Put a heater in a room with a low vent and a high one. A plume rises from the heater, entraining air as it goes, spreads under the ceiling, and a warm layer forms and drains through the top vent. Double the heating and the plume carries more, and the layer's warmer, so its outflow is faster, and the two changes exactly cancel. The height of the warm layer's lower edge does not change at all. Linden and his colleagues found in 1990 that it depends on the vents' area and the room's height and on nothing else, which means a building can be sized for a clear breathing zone without knowing how many people will be in it.

Worth reading first: How far a parcel gets · Above a warm wire the plume speeds up as it rises.

The essays on how far a parcel gets and its successors followed turbulent mixing as a matter of statistics. There’s another way of describing how a turbulent stream mixes with its surroundings, far cruder and far more useful, and it’s what Morton, Taylor and Turner came up with in 1956. A plume rising from a small hot source doesn’t need a detailed model of its turbulence. All that needs to be assumed is that the outer fluid’s drawn in at a rate proportional to the plume’s own velocity. Their paper gave a formula for the plume’s flow. Its constant, called the entrainment coefficient, can be measured once and thereafter trusted.

That formula, put inside a box, gives one of the most surprising results of practical fluid mechanics. Baines and Turner in 1969 put a plume in a sealed box and predicted how a stratified fluid builds up from the ceiling down. In 1990, Linden, Lane-Serff and Smeed put vents in the box and found that the steady state’s a sharply divided two-layer room. The cool lower layer is air from outside. The warm upper layer has been drawn through the plume. It’s the interface between them that a person’s head sits below, or above. Its height can be computed in one line, and when that’s done, the heat load cancels out.

That’s a strange thing to find in a building calculation. Heat is what’s driving the whole flow. Yet it doesn’t decide where the boundary between the two layers is.

The interface height depends on the vents and the ceiling, and the heat has cancelled out of the equation. The steady height of the warm layer's bottom, as a fraction of the room's height, against the vents' effective area over the height squared. It reads 0.285 at 0.002, 0.503 at 0.01, 0.799 at 0.05, 0.967 at 0.2. With an entrainment constant of 0.1, C = 0.115.
Fig. 1 The steady height of the warm layer’s lower edge, as a fraction of the room’s height, against the vents’ effective area over the height squared: 0.285 at 0.002, 0.503 at 0.01, 0.799 at 0.05 and 0.967 at 0.2. With an entrainment constant of 0.1, C=0.115C=0.115.

The plume’s own law

Take a point source of buoyancy, with a flux B=gβP/ρcpB=g\beta P/\rho c_p for a heat load PP. It’s the only parameter, so dimensions alone give nearly everything. At a height zz above the source, the plume’s volume flux has to be

Q(z)=CB1/3z5/3,Q(z)=CB^{1/3}z^{5/3},

and its reduced gravity, g′=B/Qg'=B/Q, is B2/3z−5/3/CB^{2/3}z^{-5/3}/C. All that’s left is the constant, and that’s where Morton, Taylor and Turner’s entrainment comes in: the rate of inflow at the edge of the plume is a fixed fraction α\alpha of the speed on its axis. It gives

C=6α5(9α10)1/3π2/3,C=\frac{6\alpha}{5}\left(\frac{9\alpha}{10}\right)^{1/3}\pi^{2/3},

and with α\alpha measured at about 0.1, C=0.115C=0.115. The plume’s flow goes as z5/3z^{5/3}, as a rising plume collects more and more of its surroundings. Near the ceiling of a 3 m room, a plume from a 100 W source carries a flow of 0.115×(2.8×10−3)1/3×35/30.115\times(2.8\times10^{-3})^{1/3}\times3^{5/3}, or about 0.10 m³/s. So in a 3 m room, a single person’s heat, of about 100 W, entrains something like a hundred litres of air a second by the time it reaches the ceiling. That’s a surprisingly large figure. A person breathes less than a litre a second, and a ventilation rate per person of about ten litres a second is a typical specification. So a plume is drawing some ten times the fresh-air flow from the room, at head height and above. It’s why a stuffy room has such a stable layer, as the plume has far more air to entrain than the room’s ventilation is providing. It’s also the reason the plume speeds up as it rises in a laminar case, and why a turbulent one’s mean speed behaves differently.

Two vents and a cancellation

Now put that in a room of height HH with a low vent and a high vent, of combined effective area AA. In a steady state, a warm layer occupies the room above a height hh, with a uniform reduced gravity g′g'. Air leaves through the top at a rate set by the hydrostatic head across the warm layer, as in a chimney:

Qout=Ag′(H−h).Q_{\rm out}=A\sqrt{g'(H-h)}.

The warm layer is being supplied by the plume at the height where the plume reaches it, Q(h)=CB1/3h5/3Q(h)=CB^{1/3}h^{5/3}, with a reduced gravity g′=B2/3h−5/3/Cg'=B^{2/3}h^{-5/3}/C. Equate the two flows:

CB1/3h5/3=AB2/3Ch5/3(H−h).CB^{1/3}h^{5/3}=A\sqrt{\frac{B^{2/3}}{Ch^{5/3}}(H-h)}.

Look at the BB on each side. The left has B1/3B^{1/3}, the right has B2/3=B1/3\sqrt{B^{2/3}}=B^{1/3}. They cancel. With ξ=h/H\xi=h/H,

AH2=C3/2ξ51−ξ.\frac{A}{H^2}=C^{3/2}\sqrt{\frac{\xi^5}{1-\xi}} .

There’s no heat load anywhere in it. The height of the interface is a function of the geometry and of one measured constant.

Add heat and the warm layer gets warmer, and its lower edge stays where it wasFor a 3 m room with A/H² = 0.02, the interface stands at 1.88 m. It stays there whatever the load, and the layer's temperature rise goes as the two-thirds power: 1.12 K at 50 W, 5.21 K at 500 W, 24.2 K at 5000 W.10²10³024681012heat load, wattsinterface in m, temperature rise in Kinterface height, mlayer's rise, Ka turbulent plume's entrainment in a room, a warm layer's buoyant outflow through two ventsGrashof number large, a turbulent plume from a point, mixed by entrainment
Fig. 2 For a 3 m room with A/H2=0.02A/H^2=0.02, the interface stands at 1.88 m whatever the load, and the layer’s temperature rise goes as the two-thirds power: 1.12 K at 50 W, 5.21 K at 500 W, 24.2 K at 5,000 W. Dialled through 0.005, 0.02 and 0.08, the vents move the interface and the temperature together, and the load only moves the temperature.

It’s worth seeing the reason in physical terms. More heat means a stronger plume, carrying more air, which would tend to deepen the layer. Yet it also makes the warm layer warmer, and so increases the buoyant head at the outflow, in just the same proportion. A plume carries flow as B1/3B^{1/3}, and a chimney carries flow as the square root of buoyancy, which is itself B2/3B^{2/3}. Those are the same power, and it’s an accident of the plume’s dimensional form. Had the source been a line rather than a point, Q∝B1/3zQ\propto B^{1/3}z and g′∝B2/3/zg'\propto B^{2/3}/z, and the same cancellation occurs. So this isn’t a coincidence of the three-dimensional plume but something a little deeper: both have to scale with a buoyancy velocity (Bz)1/3(Bz)^{1/3} when no other velocity’s available, and the chimney’s velocity is the same one. In both, the velocity in question is set by buoyancy alone. Whatever else happens, the room hasn’t got another velocity scale to compare it with. Wind would provide one, and wind does break this result. The speed nobody imposed has been the theme of natural convection all along, and this is it at the scale of a building.

To test a cancellation like this, the transient has been marched here for a room, with volume and buoyancy content each conserved by a separate equation, from a nearly empty layer. The march with 100 W and the march with 1,000 W both end at ξ=0.6273\xi=0.6273, and the formula gives 0.6273. That doesn’t depend on assuming the cancellation. The different heat loads reach that point at different rates, the stronger one faster, but they end at one place.

What the designer gets

A cancellation’s only interesting if it can be used, and here it’s useful indeed.

The vent a room needs grows with the square of its height and takes no account of how many people are in it. The effective vent area, in square metres, to keep the interface at a chosen fraction of the room's height, against the height. For a 3 m room, clear to 0.75 needs 0.344 m²; a 12 m hall needs 5.5 m². Those are effective areas, with the openings' discharge coefficients still to pay.
Fig. 3 The effective vent area, in square metres, to keep the interface at a chosen fraction of the room’s height, against the height. For a 3 m room, clear to 0.75 needs 0.344 m²; a 12 m hall needs 5.5 m².

Keeping the warm layer above head height is what a naturally ventilated building’s for. In a displacement scheme, the cool lower layer is breathing air, fresh from outside. With a warm layer overhead, it’s the stale air that collects up there, with whatever’s in it from the plumes. So the interface height’s the design parameter, and it depends on the openings. Not on how many people there are, and not on what equipment is running. A lecture theatre that’s half full should have the same interface as a full one, at least in this idealisation. Its upper layer’s cooler, and that’s the whole difference. So an architect can size vents for a target height, knowing that the occupancy doesn’t enter. Several well-known naturally ventilated buildings of the 1990s were designed along these lines, with salt-bath models and this formula, and Linden’s 1999 review gives examples.

It’s also worth asking what could be done about that if the load does matter. The load’s effect on temperature goes as the two-thirds power. At 500 W, in that 3 m room, the upper layer’s only about 5 K warmer. At 5,000 W, it’s 24 K. So what the load limits is the upper layer’s temperature, and that’s a comfort issue and a matter of keeping the ceiling cool, which has to be dealt with separately. The vent area sets both of those, in opposite senses. Larger vents raise the interface and cool the layer.

There’s also an interesting consequence for how the same load is distributed.

Spread the same heat among many sources and the warm layer's edge comes down. The interface height with n equal sources at a fixed vent of A/H² = 0.02, with no change in the total load. It reads 0.627 at n = 1, 0.366 at n = 5, 0.219 at n = 20. Each source now has its own plume, entraining on its own, and the same flux is delivered at less height. The total load has still cancelled.
Fig. 4 The interface height with nn equal sources at a fixed vent of A/H2=0.02A/H^2=0.02, with no change in the total load: 0.627 at n=1n=1, 0.366 at n=5n=5 and 0.219 at n=20n=20.

With nn equal sources, each has its own plume, with B/nB/n, and Linden and Cooper’s 1996 analysis gives the result with an nn inserted in front of the formula, A/nH2A/nH^2. So twenty sources of 50 W have an interface at about a fifth of the height, and one of 1,000 W has one at 0.63 of it. It’s the entraining surface area that counts. Twenty thin plumes entrain more air than a single strong one, at any height, and so they fill the room down further. A crowd of people should be considered as many plumes and a single heater as one. Equivalently, spreading the heat is what brings the warm layer down. A wholly distributed source, like a warm floor, has no interface at all, and it mixes the room. That’s an interesting result for an engineer to set against intuition: the distribution of a heat load matters, and its size doesn’t.

The sealed room, and a front that slows down

Without the vents, the room’s a filling box, in which nothing leaves. The first plume air reaches the ceiling and spreads as a thin layer, and each new arrival lifts the previous. The bottom edge of that layer falls at a rate given by the plume’s flow at that height, over the room’s area SS:

Sdhdt=−Q(h)=−CB1/3h5/3.S\frac{dh}{dt}=-Q(h)=-CB^{1/3}h^{5/3}.

In a sealed room the first front falls quickly at first, then ever more slowly as the plume below it thins. The first front's height over the room's, against time in units of S/(C B¹ᐟ³ H²ᐟ³). From the ceiling, it reaches half-height at 0.881 of those units, a fifth at 2.89, and a twentieth at 9.55. A plume near its source has little flow to bring down.
Fig. 5 The first front’s height over the room’s, against time in units of S/CB1/3H2/3S/CB^{1/3}H^{2/3}. From the ceiling it reaches half-height at 0.88 of those units, a fifth at 2.9, and a twentieth at 9.6.

The front falls quickly at first and then increasingly slowly. A plume near its source has little flow to send down, so the front approaches the source only asymptotically. For a 3 m room of 25 m² with 100 W, the time unit is about twelve minutes. The room’s stratification becomes roughly stationary in shape after that, while its temperature continues to rise uniformly. That’s Baines and Turner’s asymptotic state. It’s why a room’s vertical temperature profile has its known form after a time, independent of the initial conditions, as a turbulence might forget its start. In a real building, of course, sealed rooms have leaks, and the time scale’s usually comparable to the air change rate.

Nothing above used details of the turbulence in the plume, except the one constant. So it’s fair to ask how far this can be trusted. It’s the same reasoning as the wall law’s indifference to what’s inside its layer, and the same weakness. The entrainment constant is measured for an unbounded plume in a uniform environment. Inside a real room, plumes are bent by any flow, and the plume’s own impact on the interface mixes some warm air down.

Why this particular power, and why it had to be

The cancellation was presented above as an algebraic accident that survives in two dimensions. It isn’t an accident, and a dimensional argument shows it. The whole steady state has just four quantities in it: BB, HH, hh and AA, with the entrainment constant as a pure number. Buoyancy flux has the dimensions of length to the fourth over time cubed. It’s the only one of these with a time in it. So if the interface’s height h/Hh/H is to be a dimensionless function of the others, BB can’t appear, for there’s nothing to cancel its seconds against. There’s only one thing in the problem that knows what a second is, and a dimensionless answer can’t contain it.

That’s a clean and complete argument, and it says something about when the cancellation must fail. Bring in anything else with a time in it, and BB can appear. A wind has a velocity, so an interface has a Froude number in it. A heater that’s turned on has a time since it was turned on. A room’s walls have a thermal time. A background stratification has a buoyancy frequency. An imposed mechanical ventilation rate has a flow. Any one of those, and the heat load comes back. It’s the sort of result that dimensional analysis can reach, and a reader who has seen π\pi-groups can see it at once. Nobody needs to go through the algebra.

It’s also why the temperature does depend on load. Temperature rise is a reduced gravity, with seconds in it. It can’t be a function of geometry alone, and so it’s forced to go as B2/3B^{2/3}, which is the only power that makes its dimensions work. Since the velocity of the outflow is (BH)1/3(BH)^{1/3} in scale, the time for the room to reach its steady state is a length over that velocity, S/(B1/3H2/3)S/(B^{1/3}H^{2/3}). All that’s been chosen by dimensions, and the only thing left to physics has been the shape of the function of ξ\xi, and the value of CC.

Comparing with a similarity solution elsewhere brings out a further point. The self-similar jet is exact in its total and leaves its entrainment rate undetermined, and here too it’s entrainment that remains after dimensions have said all they can. That one constant, α\alpha, then enters only through the factor C3/2C^{3/2} in a design formula. It’s measured at about 0.1 in a plume and 0.05 or so in a jet, and that’s a remaining uncertainty. It’s rather surprising that a room’s ventilation should depend on so little.

An old idea in a new setting

Entrainment is a surprisingly robust idea, far beyond buildings. It’s the same closure that a jet in a duct and a stratified layer rely on, and the “filling box” has appeared in magma chambers and in a sea basin filling with dense bottom water. A very wide range of large-scale flows appears to follow it. Deep water in an ocean basin, formed in small polar regions and sinking as plumes, gives the abyssal stratification in the Munk and Stommel models, with filling-box dynamics as a candidate mechanism. A large cooling pond or a molten pool in solidifying metal shows the same behaviour. Any time a localised source of buoyancy feeds a confined basin, the box arises, and the stratification has a characteristic form, since a plume’s entrainment rate sets what height receives which fluid.

Then there’s a practical modern concern of the same form. Airborne infection in rooms depends on exactly this two-layer structure. In a well-stratified room, exhaled air from a person’s breathing plume may rise to the warm layer and stay there, or it may be trapped at the interface if the plume’s breath is too cool to reach it. The separation between layers is what makes displacement ventilation so good at removing contaminants, when the sources and people are all below the interface. Sometimes, though, a low interface can trap exhaled air at breathing height. A recent body of work has examined this question, and it’s a place where the interface’s insensitivity to load has a further practical side.

What the box cannot show

Wind. Almost all natural ventilation has some wind acting on it. Hunt and Linden gave the two-layer solution with a wind pressure in 2001. Assisting wind increases the flow, so the interface rises, and now the load does matter, since it’s competing with a velocity not set by itself. An opposing wind can reverse the flow, and it can give rise to multiple steady states. So the heat load’s disappearance is only true when buoyancy’s the sole driver.

Mixing at the interface. The plume passes through the interface and brings cool air into the warm layer, and the warm air’s motion and a plume’s impact on the ceiling stir the layer and the interface. Real interfaces have thickness and their heights differ a little from this one. The interface isn’t perfectly sharp, as is obvious if a salt-bath experiment’s watched closely.

The source’s own size and momentum. A person isn’t a point. A real source’s plume has an initial width, and a virtual origin below the actual source. It’s normal for this to be a correction of a few tens of centimetres, which for a 3 m room isn’t small. Ventilation plumes also carry initial momentum, in a way that changes the near-source flow.

Heat transfer through walls. The warm layer loses heat to the walls and ceiling, and to the floor by radiation. Radiation from the warm ceiling to the floor, in a real room, heats the lower layer, which violates the assumption that the lower layer’s at ambient temperature. It’s a large effect in many real buildings.

Anything the figures aren’t drawing. All the figures are of a one-dimensional state. No plume or layer is drawn. They’re the output of an algebraic statement, and it’s a simplification of a flow that’s fully three-dimensional and full of unsteady motions at the interface.

The convention

BB is the buoyancy flux in m4/s3\mathrm{m^4/s^3}, here from B=gP/ρcpTB=gP/\rho c_pT, and PP is the heat load in watts, in air at 293 K. HH is the room’s height, measured from the source to the upper vent. hh is the interface’s height above the source and ξ=h/H\xi=h/H. AA is an effective area that combines top and bottom openings with their discharge coefficients, defined by the standard formula for two vents in series. All flows are per second and the entrainment coefficient is 0.1 throughout, with CC from that value. “Rise” is the upper layer’s temperature over the outdoor air’s.

Marching to the formula

The filling box's numbers, and the checks on them. The plume's constant; a transient march of a room to its steady state at 100 W and at 1000 W, against the formula.
Fig. 6 The plume’s constant, 0.115; a transient march at 100 W and at 1,000 W, each ending at 0.6273; and the formula’s interface at A/H2=0.02A/H^2=0.02, also 0.6273.

The march conserves volume and buoyancy content in the warm layer, and uses the two-state outflow, with no assumption that the layer’s in a steady state, so the cancellation it finds isn’t assumed. Interfaces at the top and bottom of the room are refused, as is a negative vent, and a source with no heat, in which nothing happens and the formula’s an empty statement.

Morton, Baines and Linden

Morton, Taylor and Turner’s plume paper appeared in 1956. Baines and Turner’s filling box followed in 1969, and Germeles’s numerical method in 1975. Linden, Lane-Serff and Smeed’s “Emptying filling boxes” was published in 1990, and Linden and Cooper’s study of multiple sources in 1996. Hunt and Linden’s analysis of wind appeared in 2001, and a good general review by Linden in 1999.

Still open: how a plume’s piercing moves the line

The essay has an interface that’s perfectly sharp, with nothing crossing it but the plume. The next calculation would allow the plume to entrain a fraction of the warm fluid when it reaches the interface, at the rate set by a local Froude number of the plume’s impact, and solve for the steady state with the warm layer’s own stirring. It would ask whether the load’s cancellation survives, as it can since a Froude number built from buoyancy has no load in it either, and how far the interface moves with the mixing, because a design rule’s reliability depends less on the constant than on whether it’s still only the geometry that matters.

What links here

Computed from the collection rather than written here: the essays that point at this one.

Reads more easily once this is understood