Transition and turbulence

Stirring the interface moves the warm layer, but not with the heat

A heater in a room vented high and low builds a warm layer whose lower edge stands where the vents put it, whatever the heat — if the interface is sharp. A real plume arrives at the interface turbulent and stirs cool air up into the layer, which the vents must then also discharge, so the edge comes down. It comes down by the same fraction at every heat load, because a plume meets its interface at one Richardson number whatever it carries, and in every steady reading it is indistinguishable from a plume that simply entrains faster. What does make the edge follow the heat is a source with a fan in it, stirred or not.

Worth reading first: A room's warm layer stands where the vents say, whatever the heat · What a jet keeps, and what it collects.

A room’s warm layer stands where the vents say, whatever the heat put a heater in a room with an opening near the floor and another near the ceiling. A plume rises from the heater, entraining room air as it goes, spreads under the ceiling into a warm layer, and the layer drains through the top vent while cool air enters below. In the steady state the warm layer’s lower edge stands at a height that depends on the vents’ area and the room’s height and on nothing else. Double the heat and the plume carries a little more air and the layer is warmer, so it drains faster, and the two changes cancel exactly. Linden, Lane-Serff and Smeed found that in 1990, and it is what lets a building’s ventilation be sized for a clear breathing zone without knowing how many people will be in it.

The essay’s interface was perfectly sharp: nothing crossed it but the plume. A real plume reaches the interface as a turbulent column of air moving at tens of centimetres a second, and where it enters the warm layer it stirs the boundary, lifting cool air from below into the layer. That air joins the layer and has to leave through the top vent too. The question it left was whether the cancellation survives — whether the stirring, which might be expected to grow with the plume’s strength, makes the edge depend on the heat after all.

What the plume brings to the interface

The plume is the standard one, Morton, Taylor and Turner’s of 1956: a column whose volume flux Q=b2wQ=b^2w, momentum flux M=b2w2M=b^2w^2 and buoyancy flux F=b2wg′F=b^2wg' evolve with height as

dQdz=2αM1/2,dMdz=FQM,F=constant,\frac{dQ}{dz}=2\alpha M^{1/2},\qquad \frac{dM}{dz}=\frac{FQ}{M},\qquad F=\text{constant},

with the entrainment constant α=0.1\alpha=0.1 and top-hat profiles. Whatever stirs an interface, the stirring depends on how the plume’s inertia compares with the density step it is pushing against, which is a Richardson number, Ri=g′b/w2=FQ2/M5/2\mathrm{Ri}=g'b/w^2=FQ^2/M^{5/2}. For a pure plume from a point source the fluxes go as F1/3z5/3F^{1/3}z^{5/3} and F2/3z4/3F^{2/3}z^{4/3}, and the Richardson number is 8α/58\alpha/5: a pure number, the same at every height and for every buoyancy flux. A plume carrying a kilowatt meets its interface at the same Richardson number as one carrying fifty watts.

Whatever leaves the source, the plume's Richardson number has nearly reached the pure plume's within a metre. The Richardson number of a plume, g′b/w², over the pure plume's 8α/5, against height, for a fan source blowing 0.02 m³/s through a 0.1 m radius at 200, 1000 and 5000 W, and for a natural source of the same radius. At a metre the fan's three are 0.896, 1.03 and 1.03; at two metres 0.97, 1.01 and 1.01.
Fig. 1 The Richardson number of a plume over the pure plume’s 8α/58\alpha/5, against height, for a fan source blowing 0.02 m³/s through a 0.1 m radius at 200, 1000 and 5000 W, and for a natural source of the same radius. At a metre the fan’s three are 0.90, 1.03 and 1.03; at two metres 0.97, 1.01 and 1.01.

That is true of a real source too, and more robustly than the formula suggests. A plume that leaves its source with too much momentum for its buoyancy — a forced plume, a fan’s at a small load — has a Richardson number below the pure value, and one that leaves with too little — a lazy plume, a radiator’s, or the same fan’s at a large load — has one above it. Both relax towards the pure value as they rise, because the pure plume is the state the equations are attracted to. A fan blowing 0.02 cubic metres a second through a ten-centimetre opening carries a Richardson number within ten per cent of the pure plume’s at a metre above it at 200 watts, and within three per cent at higher loads. A room’s interface is a metre or more above the source. By the time a plume reaches the interface it has forgotten what its source said about its Richardson number.

Why every plume forgets its source

The relaxation has an exact form, and it is short enough to write down. Define the plume function Γ=5FQ2/(8αM5/2)\Gamma=5FQ^2/(8\alpha M^{5/2}), which is the Richardson number over the pure plume’s. Differentiating it with the two plume equations gives

dΓdz=4αb Γ (1−Γ),\frac{d\Gamma}{dz}=\frac{4\alpha}{b}\,\Gamma\,(1-\Gamma),

a logistic equation whose only stable state is Γ=1\Gamma=1. A forced plume, Γ<1\Gamma<1, has its Richardson number pulled up; a lazy one, Γ>1\Gamma>1, pulled down; and in either case the departure from one shrinks by a factor of ee over a rise of b/4αb/4\alpha, two and a half plume radii at α=0.1\alpha=0.1. Because the radius itself grows as the plume rises, each successive factor of ee takes longer, but a plume that leaves a ten-centimetre fan opening has crossed several of them in its first metre.

The equation also says what cannot relax. It is an equation for a ratio of the fluxes, and the fluxes themselves keep their history: a plume that left its source with a large volume flux still carries that excess at the ceiling, added to everything it has entrained since. The Richardson number at the interface is set by the attractor, and the volume flux at the interface is set by the source and the height. That split — one quantity forgotten, the other remembered — is the whole of what follows.

A fraction, not a flux

So whatever the law that relates the stirring to the plume — Turner’s inverse-Richardson form, a power of the Froude number, a measured curve — it takes the same value at every interface the plume reaches. The interface entrains a fixed fraction ε\varepsilon of the plume’s own flux. The warm layer then receives Qp(1+ε)Q_p(1+\varepsilon), its buoyancy is diluted to B/(Qp(1+ε))B/(Q_p(1+\varepsilon)), and the vents must discharge the larger flux at the smaller buoyancy. Writing the steady balance through again gives Linden’s law with one factor changed:

AH2=C3/2(1+ε)3/2ξ51−ξ,\frac{A}{H^2}=C^{3/2}(1+\varepsilon)^{3/2}\sqrt{\frac{\xi^5}{1-\xi}},

where ξ\xi is the edge’s height as a fraction of the room’s. The buoyancy flux BB has cancelled again, and for the same reason as before: the plume’s flux grows as B1/3B^{1/3}, the layer’s buoyancy as B2/3B^{2/3}, the drainage as the square root of the buoyancy times the flux it must carry, and all three move together. The stirring adds a constant factor to the flux and leaves the powers alone.

Stirring the interface lowers the warm layer's edge by the same fraction at every heat load. The height of the warm layer's lower edge as a fraction of the room's, against the effective vent area over the height squared, for a pure plume whose interface entrains a fraction of its own flux of 0, 0.1, 0.2 and 0.5. At A/H² = 0.01 the edge is at 0.503, 0.48, 0.459 and 0.409; no heat load appears in any of the four laws.
Fig. 2 The height of the warm layer’s edge as a fraction of the room’s, against the effective vent area over the height squared, for a pure plume whose interface entrains 0, 0.1, 0.2 and 0.5 of its own flux. At A/H2=0.01A/H^2=0.01 the edge is at 0.503, 0.480, 0.459 and 0.409; no heat load appears in any of the four laws.

The edge comes down. At a vent area of one hundredth of the room’s height squared, an interface entraining a tenth of the plume’s flux lowers the edge from half the room’s height to 0.48, a fifth lowers it to 0.46, and a half to 0.41. In a three-metre room those are seven, thirteen and twenty-eight centimetres: the stirring costs some of the breathing zone, and a designer who wanted the edge above head height would want a little more vent area. But the curve is the same at every load. The stirring moves the line; it cannot make the line ask about the heat.

A stirred room reads as a faster plume

The law has another consequence, which is less comfortable. The factor (1+ε)(1+\varepsilon) multiplies CC, the plume’s own constant, and CC is proportional to α4/3\alpha^{4/3}. So a room whose interface entrains a fraction ε\varepsilon is indistinguishable, in its steady edge height, from a room with a sharp interface and a plume whose entrainment constant is α(1+ε)3/4\alpha(1+\varepsilon)^{3/4}.

A stirred interface reads exactly as a plume that entrains a little faster. The plume entrainment constant a reading of the room as a sharp filling box would infer, α(1 + ε)³ᐟ⁴, against the fraction ε of the plume's flux entrained at the interface; the interface height and the layer's temperature it predicts are those of the stirred room exactly. A tenth entrained reads as α = 0.107, a fifth as 0.115, a half as 0.136.
Fig. 3 The plume entrainment constant a reading of the room as a sharp filling box would infer, α(1+ε)3/4\alpha(1+\varepsilon)^{3/4}, against the fraction entrained at the interface. A tenth entrained reads as α=0.107\alpha=0.107, a fifth as 0.115, a half as 0.136; the edge height and the layer’s temperature are those of the stirred room exactly.

It is not only the edge. The layer’s temperature, which is the other thing a ventilation engineer measures, is B/(Qp(1+ε))B/(Q_p(1+\varepsilon)) — the same as a sharp room’s with the larger constant. The filling of a sealed room, the first front descending as Qp(1+ε)/SQ_p(1+\varepsilon)/S once the layer has formed, is the same again. Every steady or slowly varying reading of a room scales with C(1+ε)C(1+\varepsilon), and a room cannot tell a plume that entrains faster from an interface that is stirred. A tenth entrained reads as an entrainment constant of 0.107 instead of 0.100, which is well inside the spread of the constants measured for free plumes, where top-hat values from 0.08 to above 0.12 have been reported depending on the experiment and the profile assumed.

That is the honest reading of the filling-box experiments that confirmed Linden’s law. Their agreement with an entrainment constant near 0.1 says that the stirring of the interface plus the plume’s own entrainment add up to that, and no experiment of that kind could have separated the two. Separating them needs a measurement of the plume itself — its flux at the height of the interface, with the room’s warm layer present and absent — and that is a measurement of a different kind.

A source that only knows its heat

The cancellation was proved above for a pure plume from a point. A heater has a size, and the air leaving it has a speed of its own. The argument still holds, and the reason is dimensional. A natural source — a radiator, a person, a lamp — has two parameters, its buoyancy flux and its size, and the speed of the air leaving it is set by its own buoyancy. Every plume quantity can then be written as the cube root of the buoyancy flux times a function of height and size, the Richardson number at any height is a function of height and size alone, and the interface’s stirring, the plume’s flux and the layer’s drainage all scale exactly as for a point. Size changes where the edge stands; heat does not.

A natural source's warm layer stands still as the load rises, stirred or not; a fan's rises, stirred or not. The height of the warm layer's edge in a 3 m room with 0.09 m² of effective vent area, against the heat load, for a natural source of 0.1 m radius and for a fan source blowing 0.02 m³/s through the same opening, each with a tenth of the plume's flux entrained at the interface and without. The natural source's edge is 0.331 at 200 W and 0.331 at 5 kW; the fan's 0.172 and 0.348.
Fig. 4 The warm layer’s edge in a 3 m room with 0.09 m² of effective vent area, against the heat load, for a natural source of 0.1 m radius and a fan source blowing 0.02 m³/s through the same opening, each with a tenth of the plume’s flux entrained at the interface and without. The natural source’s edge is 0.331 at 200 W and at 5 kW; the fan’s rises from 0.172 to 0.348.

The natural source of ten centimetres’ radius holds its edge at 0.331 of the room’s height from 150 watts to ten kilowatts, with a tenth of its flux stirred into the layer; without the stirring it holds 0.356, also at every load. It stands well below the point source’s 0.503, because a source of finite size launches a plume that already carries air, which the room’s vents must also discharge, and that is a statement about the heater’s size and nothing else.

The fan that breaks it

A fan heater is different. Its fan sets the volume of air it blows, whatever the heat, so its source has a third parameter — a volume flux, or a speed — that does not scale with the cube root of the heat. At a small load the fan’s air dominates the plume, which carries a great deal of air for its buoyancy; the layer it builds is large and cool, and its edge is low. At a large load the buoyancy takes over, the plume forgets its fan, and the edge rises towards the natural source’s.

The more air the fan moves, the lower the edge at a small load and the longer it takes the load to winThe height of the warm layer's edge against the heat load for a fan source blowing 0.02 m³/s through a 0.1 m radius in the same room, with a tenth of the plume's flux entrained at the interface. The edge is at 0.172 at 200 W, 0.285 at 1 kW and 0.367 at 10 kW; a natural source of the same size holds 0.331 at every load.10³10⁴00.10.20.30.40.5heat load, Wedge height ÷ room heightnatural sourcefan, 0.02 m³/stop-hat plume equations, α = 0.1, from a floor source into a room vented high and low; ε of the plume's flux entrainedGrashof number large, a turbulent plume, steady; the interface stirred, ε = ε₀ Ri₀/Ri
Fig. 5 The edge against the heat load for a fan source blowing 0.02 m³/s through a 0.1 m radius in the same room, with a tenth of the plume’s flux entrained at the interface: 0.172 at 200 W, 0.285 at 1 kW and 0.367 at 10 kW. Dialled to 0.005, 0.01 and 0.03 m³/s, the edge runs from 0.373 to 0.432, from 0.307 to 0.407, and from the floor at 200 W to 0.331 at 10 kW.

The fan blowing 0.02 cubic metres a second puts the edge at 0.17 of the room’s height at 200 watts and 0.35 at five kilowatts — a factor of two over the range a heater’s thermostat moves through. Stirred or not makes little difference to that: the sharp interface gives 0.205 and 0.373, the stirred one 0.172 and 0.348. The Richardson number at the interface is within a few per cent of the pure value at every load above 200 watts, so the stirring takes nearly the same fraction everywhere and shifts the curve down without changing its slope. What tilts the curve is the fan’s volume flux, carried up the plume and never forgotten. At 0.03 cubic metres a second and 200 watts the fan blows more air than the vents can drain at the layer’s small buoyancy, and the warm layer fills the room to the floor.

The load enters through the source, not the interface. The plume forgets its source’s Richardson number within a metre and never forgets its source’s volume of air.

What a designer can take from it

For a room heated by people, equipment and radiators — sources whose air is driven by their own heat — Linden’s rule can be used at any load, with the edge a little lower than a sharp interface would give. The stirring’s share can be absorbed into the plume constant used for design, and the constant measured in rooms rather than in free plumes is the one that already contains it. For a room heated by fan units, or ventilated by a supply that blows air at a fixed rate and a temperature that changes with the load, the rule fails, and fails in the unsafe direction at low load: the layer is deepest when the heat is smallest, and a breathing zone designed at full load can be lost at part load. The fix the calculation suggests is not more vent area but a source whose flow follows its heat, or a fan run at a speed that does.

Where the model stops

The interface’s stirring is reduced here to one number, a fraction of the plume’s flux, set by the Richardson number, and its value — a tenth, in the figures — is chosen rather than measured. Nothing in the argument for the cancellation depends on the value, only on the fraction’s being a function of the Richardson number, and for a fan source the load dependence is the source’s, with the stirring a minor correction. The interface is taken as sharp apart from the stirring, the warm layer as well mixed, and the plume as unaffected by the layer it passes through above the interface. A room’s walls heated by the layer, a second source at another height, or a wind at the vents — each of which introduces a scale not set by the heat — would each move the edge with the load, and none is in the model.

The convention the numbers are in

Plume quantities are top-hat and written without the factor of π\pi, so the volume flux is b2wb^2w; the room’s areas and fluxes carry it. The entrainment constant is 0.1 and C=0.116C=0.116 in Linden’s law, which carries the π\pi. A heat load PP in watts is a buoyancy flux gP/(ρcpT)gP/(\rho c_pT), about 2.8×10−5 m4 s−32.8\times10^{-5}\,\mathrm{m^4\,s^{-3}} per watt for room air. The room is 3 metres high with 0.09 m² of effective vent area, A/H2=0.01A/H^2=0.01. A natural source’s air leaves it at (F/b0)1/3(F/b_0)^{1/3}; a fan source’s at its volume flux over its area. The interface’s entrained fraction is ε=ε0 Ri0/Ri\varepsilon=\varepsilon_0\,\mathrm{Ri}_0/\mathrm{Ri} with ε0=0.1\varepsilon_0=0.1 and Ri0=8α/5\mathrm{Ri}_0=8\alpha/5, the pure plume’s.

The calculation behind the curves

A stirred interface: the checks. The plume march from a point against the pure plume's closed form, its Richardson number against 8α/5 at two loads, the stirred room against a sharp one with the apparent constant, and a natural source's edge at two loads against a fan's.
Fig. 6 The plume equations marched from a point against the pure plume’s closed form, the marched Richardson number against 8α/58\alpha/5, the stirred room against a sharp room with the apparent constant, a natural source’s edge at 200 W and 3 kW, and a fan’s.

The plume equations are marched by fourth-order Runge–Kutta in height from the source. Started from a point, the march reproduces the pure plume’s flux to seven parts in a million at two and a half metres and its Richardson number to rounding, which checks both the equations and the value 8α/58\alpha/5. The steady edge is found by bisection on the height at which the vents’ drainage of the layer’s flux at its buoyancy equals the flux the plume and the interface deliver. The stirred room’s edge agrees with a sharp room’s at the apparent constant to a part in a billion, which is the identity the indistinguishability rests on; a natural source’s edge at 200 watts and 3 kilowatts agrees to rounding; and a fan’s differs by a fifth of the room’s height, which is the check that the calculation can see a load dependence when there is one.

Who stirred the interface first

Morton, Taylor and Turner wrote the plume equations in 1956, and Baines and Turner filled a box with one in 1969. Linden, Lane-Serff and Smeed’s emptying-filling box appeared in 1990, and with it the result that a room’s stratification is set by its geometry. Turner’s laboratory work of the 1960s and 1970s on entrainment across density interfaces, Kumagai’s 1984 experiments on plumes and jets striking a stratified interface, and Baines’s on penetrating plumes are where the interfacial laws come from; Cooper and Hunt, and Kaye and Hunt, extended the emptying-filling box in the 2000s to the interfacial mixing and the source conditions considered here. The plume’s convergence towards its pure state, whatever its source, is Hunt and Kaye’s analysis of lazy and forced plumes of 2005, and what a jet keeps is the same conservation, without the buoyancy, for a jet.

Still open: a heater that is also a wall

Every source here is at the floor and everything warm is in the layer. A heated room has warm walls too, and a wall heated by the layer above the interface sheds a boundary layer that runs down it — a cool one, if the wall loses heat outside — and carries air across the interface the other way. The next calculation would add a wall plume, a line plume whose buoyancy flux is set by the wall’s heat loss and so by the layer’s temperature, falling from the ceiling into the lower layer, and ask whether the wall’s flux, which grows with the layer’s temperature and so with the heat load, is the scale that finally makes the edge depend on the load in a room with no fan — and how large a wall’s heat loss has to be, against the source’s heat, for the dependence to be seen.